Burner main parameter setting and method

Baltur Burner main parameter setting and method

Pressure before the pressure regulating valve: 0~04MPaas

b. The pressure adjusted by the pressure regulating valve: TBG45-85PV: 4-6KPa; TBG120-210P: 10Kpa BGN250, 300, 350: 15KPa

Wind pressure switch: 04~1mbar;

d Gas switch: 50mbar (special exception);

e. Gas low pressure switch: 2.5mbar;

f. Self-gas switch: the pressure setting value is adjusted to half of the pressure of the natural gas supply pipe network

g service motor: I():70(6070); off):0

I(min): 20 (0~20) IV(ignition): 30 (20~50)

h. Head air control button: big mouth: about 2.5; small mouth: about 11.5