More Causes and solutions of light oil burner failures

Causes and solutions of light oil burner failures

Fault

Causes

Suggested solutions

The burner cannot burn large fires

Control system TR is not closed.

 Adjust or replace

The controller is broken.

Replace it.

The second stage solenoid valve is broken.

Replace it.

Hydraulic cylinder is broken.

Replace it.

The second nozzle injects fuel but the damperUnable to reach damper position

Pump pressure low

Increase it

Hydraulic cylinder is broken.

Replace it.

Unstable fuel supply

If it is due to pump or oil system conduction
Sincerely,  Please check the reason

Keep the fuel tank close to the burner

There is rust in the oil pump

There is water in the oil tank.

Drain the water in the oil tank.

There is noise and the oil pressure is unstable.

There is air in the oil inlet pipe. .

Tighten the joint

Negative pressure value is too high
(above 35cmHg)

The height difference between the fuel tank and the burner is too large.

 Use an annular oil line to connect the burner.

Pipe diameter is too small

Increase it

Filter clogged

Clean it

Oil inlet valve closed

open it

The temperature is too low and wax precipitates.

Add additives to the light oil.

Pump does not start after long interruption

The oil return pipe is not immersed in oil..

 Return it to the height of the oil inlet pipe

Air intake in the oil inlet pipe.

Tighten the joint.

Oil leakage from pump

Oil leakage from sealing parts

 Replace pump

Smoke - black smoke

Insufficient air

Adjust combustion damper according to regulations

The nozzle is worn or dirty.

Replace it.

The nozzle filter is clogged.

Clean or replace it.

The pump pressure is incorrectly adjusted.

 Adjust it to 10-14bar.

The fan is dirty.

 Clean it.